Back to Product
FAQ

How does the KTI01003001E2DI handle emergency override signals and door-ajar conditions?

Answer:
The unit features a dedicated emergency input that latches both doors open indefinitely until manually cleared via the onboard tactile reset button, as well as an audible long beep if a door remains unclosed after 2 minutes.

The KTI01003001E2DI controller incorporates dedicated hardware logic to handle life safety and security exceptions:

  • Emergency Override Function: Dedicated inputs on CON1 (Pin 11 for Emergency Exit I/P and Pin 12 for GND) accept connections from break-glass units or master emergency release switches. When triggered, the controller immediately forces both door lock outputs to an unlocked state continuously. Normal sequential interlocking logic is suspended indefinitely until an operator physically presses the onboard tactile RESET push button switch.
  • Door Ajar / Timeout Alarm: If a monitored door does not return to its closed state and provide feedback through the door sensor inputs within 2 minutes of opening, the controller automatically triggers an internal audible alarm ("Long beep") to alert facility personnel of an interlock breach or mechanical door obstruction.