Field Wiring and Terminal Setup Guide

Power Supply and Primary Terminal Block (CON1) Wiring

The KTI01003001E2DI Interlocking System 2 Door Controller operates from a regulated 12V DC power source. Power leads must be terminated directly into the 12-pin terminal block designated as CON1. Terminate the positive lead to CON1 Pin 1 (+Ve Supply Adapter 12V) and the negative return to CON1 Pin 2 (-Ve Supply Adapter 12V). Ensure proper polarity before energizing the board.

Digital trigger inputs for access control readers, exit switches, and push-buttons interface through the remaining terminals on CON1. Each operational input is paired with an adjacent ground reference terminal:

  • Door 1 Entry Trigger: Connect dry-contact switch or reader relay output across Pin 3 (1st Door Entry I/P) and Pin 4 (GND).
  • Door 1 Exit Trigger: Connect exit button across Pin 5 (1st Door Exit I/P) and Pin 6 (GND).
  • Door 2 Exit Trigger: Connect exit button across Pin 7 (2nd Door Exit I/P) and Pin 8 (GND).
  • Door 2 Entry Trigger: Connect dry-contact switch or reader relay output across Pin 9 (2nd Door Entry I/P) and Pin 10 (GND).
  • Emergency Release Input: Connect an emergency break-glass unit or latching switch across Pin 11 (Emergency exit I/P) and Pin 12 (GND).

Door Position Feedback and Lock Relays (CON2)

Sequential interlocking logic requires real-time closed/open status monitoring of each portal. Magnetic reed door position sensors and locking hardware wire into the 10-pin terminal connector designated as CON2.

Wire the normally closed (NC) dry contacts from the door status contacts to the designated sensor pins. Connect the Door 1 sensor across Pin 1 (Door Sensor 1 NC) and Pin 2 (Door Sensor 1 COM). Connect the Door 2 sensor across Pin 3 (Door Sensor 2 NC) and Pin 4 (Door Sensor 2 COM). If a door remains physically open beyond 2 minutes without sensor contact closure, the controller sounds a continuous long beep alarm.

Lock hardware connects to the isolated Form C relay contacts on CON2. For fail-safe hardware (such as magnetic locks requiring power to remain locked), wire through the NC and COM terminals. For fail-secure hardware (such as drop bolts or strikes that release upon power application), wire through the NO and COM terminals:

  • Lock Output 1: Pin 5 (NO), Pin 6 (COM), Pin 7 (NC).
  • Lock Output 2: Pin 8 (NO), Pin 9 (COM), Pin 10 (NC).

Hardware DIP Switch Delay Configuration

Before commissioning, configure the unlock duration using onboard DIP switch positions 2, 3, and 4. Set the switches to achieve the required door release interval:

Switch 2Switch 3Switch 4Output Delay Duration
OFFOFFOFF5 Seconds
OFFOFFON5 Seconds
OFFONOFF10 Seconds
OFFONON15 Seconds
ONOFFOFF20 Seconds
ONOFFON25 Seconds
ONONOFF30 Seconds
ONONON35 Seconds

Emergency Override and Diagnostic LED Verification

When the emergency trigger on CON1 (Pins 11 and 12) is initiated, both door lock relays instantly release and remain permanently open. To clear the latch and restore interlock control, press the onboard tactile RESET push button.

Validate field wiring during power-up by observing the onboard diagnostic LEDs. Verify that the PWR LED lights continuously and the HB (Heartbeat) LED blinks to confirm active microprocessor operation. Test individual peripheral circuits by confirming that L1 (Door 1 Entry), L2 (Door 1 Exit), L3 (Door 2 Exit), and L4 (Door 2 Entry) illuminate when corresponding inputs short to GND. Verify relay switching by observing L6 (Lock 1 Output) and L7 (Lock 2 Output), as well as L5 (Emergency Input) and L10 (Emergency Output) during override testing.