Back to Product
Compatibility

Hardware Compatibility and Peripheral Integration

The KTI01003001E2DI Two Door Interlock Controller is engineered to interface seamlessly with industrial and commercial access control peripherals, locking devices, door position monitors, and life safety emergency systems. Equipped with two onboard Form C relay outputs and dedicated digital signaling channels, the controller delivers flexible integration across cleanroom airlocks, corporate facilities, server rooms, hospitals, and high-security zones.

Locking Hardware and Form C Relay Interfaces

The controller provides two independent Form C relay outputs terminated at connector CON2, supporting both fail-safe and fail-secure locking mechanisms:

  • Fail-Safe Hardware (Electromagnetic Locks): Magnetic locks (EM locks) that release upon power interruption connect directly across the Common (COM) and Normally Closed (NC) terminals. Lock 1 utilizes CON2 Pin 6 (COM) and Pin 7 (NC), while Lock 2 utilizes CON2 Pin 9 (COM) and Pin 10 (NC).
  • Fail-Secure Hardware (Electric Strikes & Solenoid Drop Bolts): Motorized bolts and electric strikes requiring an energized pulse to unlock wire across the Normally Open (NO) and Common (COM) terminals. Lock 1 utilizes CON2 Pin 5 (NO) and Pin 6 (COM), while Lock 2 utilizes CON2 Pin 8 (NO) and Pin 9 (COM).

Relay unlock durations are configurable via onboard 3-bit DIP switches (positions 2, 3, and 4) to support lock release delays of 5s, 10s, 15s, 20s, 25s, 30s, or 35 seconds, accommodating diverse lock actuation profiles.

Access Peripheral and Trigger Input Compatibility

Terminal connector CON1 includes four discrete digital input channels designed to interface with standard dry-contact signaling peripherals:

  • Door 1 Entry: CON1 Pin 3 (1st Door Entry I/P) paired with Pin 4 (GND).
  • Door 1 Exit: CON1 Pin 5 (1st Door Exit I/P) paired with Pin 6 (GND).
  • Door 2 Exit: CON1 Pin 7 (2nd Door Exit I/P) paired with Pin 8 (GND).
  • Door 2 Entry: CON1 Pin 9 (2nd Door Entry I/P) paired with Pin 10 (GND).

These channels are electrically compatible with normally open (NO) dry-contact relay outputs from biometric readers, RFID proximity card terminals, wave-to-exit touchless sensors, and mechanical request-to-exit (REX) push buttons.

Door Status Sensor and Feedback Integration

Sequential interlock enforcement depends on real-time door position feedback wired to connector CON2:

  • Door Sensor 1: Connects across CON2 Pin 1 (NC) and Pin 2 (COM).
  • Door Sensor 2: Connects across CON2 Pin 3 (NC) and Pin 4 (COM).

The controller requires dry-contact Normally Closed (NC) magnetic reed switches or integrated lock status sensors. If a door remains unsealed or the sensor contact does not register closure within 2 minutes of door release, the controller activates an onboard continuous long beep timeout alert to flag the breach.

Emergency System & Power Integration

Emergency override loops integrate through CON1 Pin 11 (Emergency Exit I/P) and Pin 12 (GND). This circuit interfaces with break-glass emergency call points, latching emergency mushroom switches, or fire alarm relay contacts. Triggering this input releases both doors indefinitely until the system is manually cleared via the onboard tactile RESET button switch. Primary operational power requires an external 12V DC regulated supply connected across CON1 Pin 1 (+Ve Supply) and Pin 2 (-Ve Supply).