Base Selection and Electrical Backbox Mounting
The Notifier FST-951R intelligent rate-of-rise thermal detector installs into a separate detachable mounting base, allowing field wiring to be completed and inspected prior to detector head installation. The unit is designed for direct-surface mounting or installation onto standard electrical backboxes. Any junction box or electrical backbox selected must have a minimum internal depth of 1.5 inches (3.81 cm) to accommodate field wiring terminations and the base assembly.
The detector head is mechanically interchangeable with Notifier intelligent photoelectric and ionization smoke sensors on the same base platform, simplifying system retrofits or direct replacement of legacy FST-851 Series devices. Compatible mounting bases include the standard flanged B300-6 white base (6.1-inch / 15.6 cm overall diameter), the B501 / B501-WHITE standard 4-inch (10.2 cm) European flangeless base, the B224RB-WH relay base, the B224BI-WH isolator detector base, and the B200S-WH or B200SR intelligent sounder bases.
Rotary Decimal Addressing
Before locking the detector head into the base, the installer must assign the SLC point ID address. The FST-951R features two built-in rotary decimal switches located directly on the sensor housing. Addresses are selected using a standard screwdriver to turn the rotary dials to the designated decimal address, eliminating the need for specialized electronic programmers or binary DIP switch calculations.
Signaling Line Circuit (SLC) Field Wiring
Wiring terminations are landed on the separate detector base using integrated SEMS clamping screws that secure stripped wire leads under captive pressure plates. The FST-951R operates over a two-wire SLC loop with an operating voltage range of 15 to 32 VDC peak, communicating via Notifier FlashScan protocol.
- Supervision: Due to inherent electronic supervision provided by the addressable SLC loop, end-of-line resistors (EOLRs) are not required at the detector base.
- Wiring Topologies: Wiring branch runs or "T-taps" are permissible only when the loop is engineered for Style 4 (Class B) operation. Style 6 and Style 7 (Class A) loops require continuous out-and-return wiring loops without T-taps.
- Remote Annunciation: Bases support field wiring connections to an optional RA100Z remote LED annunciator operating across a 3 to 32 VDC range.
- Back Pressure: The detector housing is molded from fire-resistant plastic and sealed against back pressure from the electrical backbox.
Detector Spacing and Environmental Criteria
Proper physical placement ensures compliance with listed thermal response thresholds (15°F / 8.3°C per minute rate-of-rise and 135°F / 57°C fixed temperature). The detector must be installed strictly within its listed operating temperature boundaries of -4°F to 100°F (-20°C to 38°C) and relative humidity limits between 10% and 93% (non-condensing).
| Parameter |
Specification / Requirement |
| UL Approved Spacing |
50 ft. (15.24 m) center-to-center |
| FM Approved Spacing |
25 ft. x 25 ft. (7.62 m x 7.62 m) |
| Minimum Backbox Depth |
1.5 inches (3.81 cm) |
| SLC Operating Voltage |
15 to 32 VDC peak |
| Peak Standby Current |
200 µA @ 24 VDC (max. average, 1 poll / 5 s with LED enabled) |
| Maximum Alarm Current |
4.5 mA @ 24 VDC (LEDs on) |
| Detector Height |
2.0 inches (5.3 cm) |
| Shipping Weight |
3.4 oz. (95 g) |
Mechanical Locking, Tamper Resistance, and Verification
The FST-951R incorporates an integral, built-in tamper-resistant feature within the base interface to prevent unauthorized removal of the sensor head. When engaged, the detector can only be released using a specialized release tool.
Once secured and powered, the unit's dual visual alarm LEDs provide a 360-degree viewing angle. The LEDs blink red upon each panel communication poll in normal standby condition and latch to a steady red illumination when an alarm threshold is crossed. Commissioning engineers can verify operation using a panel-initiated walk test with address display, a panel remote test command, or on-site testing using a functional test magnet (models M02-04-00 or M02-09-00 with telescoping handle) held against the sensor body.