Which mounting bases, accessories, and system wiring protocols work with the Notifier FST-951R?

Answer:
The FST-951R operates on Notifier FlashScan addressable SLC loops and plugs into separate bases including the B300-6 (6-inch flanged), B501 (4-inch flangeless European), B224RB relay base, B224BI isolator base, and B200S/B200SR sounder bases. It also supports connection to an optional RA100Z remote LED annunciator.

The Notifier FST-951R detector head uses plug-in architecture with a detachable base to streamline installation, maintenance, and field retrofits:

  • Compatible Bases: Mounts to standard flanged base B300-6 (white, 6-inch), flangeless base B501-WHITE (white, 4-inch), relay base B224RB-WH, isolator base B224BI-WH, and intelligent programmable sounder bases B200S-WH, B200S-LF-WH (520 Hz low frequency), and B200SR-WH.
  • Backbox Mounting: Detector bases must be installed on an electrical backbox with a minimum depth of 1.5 inches (3.81 cm). Wiring connects via SEMS clamping screws.
  • Head Interchangeability: The installed base allows direct mechanical and wiring interchangeability with Notifier addressable photoelectric and ionization smoke detector heads.
  • Loop Protocol & Wiring: Requires a Notifier FlashScan protocol SLC loop. End-of-line resistors are not required due to inherent SLC supervision. Wiring T-taps and branches are supported on Style 4 (Class B) circuits.
  • Remote Annunciation & Testing: Includes an output connection for the optional RA100Z remote LED annunciator (3 to 32 VDC). Testing can be initiated via panel command or locally using test magnets M02-04-00 or M02-09-00.