Back to Product
FAQ

What are the thermal detection thresholds and electrical specifications for the Notifier FST-951R?

Answer:
The Notifier FST-951R triggers an alarm at a rate-of-rise threshold of 15°F (8.3°C) per minute or when ambient temperature reaches a fixed 135°F (57°C). It operates over a two-wire SLC loop between 15 and 32 VDC peak, with a maximum average standby current of 200 µA at 24 VDC and a maximum alarm current of 4.5 mA at 24 VDC.

The Notifier FST-951R intelligent thermal detector incorporates dual-action thermal sensing engineered for rapid alarm signaling:

  • Thermal Thresholds: Rate-of-rise detection calibrated to 15°F (8.3°C) per minute, paired with a fixed-temperature alarm set point preset to 135°F (57°C).
  • Operating Voltage: 15 to 32 VDC peak across a two-wire Signaling Line Circuit (SLC).
  • Current Consumption: Maximum average standby current of 200 µA at 24 VDC (one communication poll every 5 seconds with LED enabled) and maximum alarm current of 4.5 mA at 24 VDC with LEDs continuously lit.
  • Operating Range: Temperature rating of -4°F to 100°F (-20°C to 38°C) with relative humidity operating between 10% and 93% non-condensing.
  • Physical Dimensions & Weight: Sensor height of 2.0 inches (5.3 cm), with diameter governed by base selection (6.1 inches / 15.6 cm with B300-6; 4.0 inches / 10.2 cm with B501). Shipping weight is 3.4 oz. (95 g).
  • Coverage Spacing: UL approved for 50 ft. (15.24 m) center-to-center spacing; FM approved for 25 ft. x 25 ft. (7.62 m x 7.62 m) spacing.