Which mounting bases, protocols, and field accessories are compatible with the Notifier FSP-951T?

Answer:
The FSP-951T communicates over Notifier FlashScan protocol loops and installs into standard plug-in bases including B300-6 (6-inch flanged white base), B501-WHITE (4-inch flangeless European base), B224RB-WH relay bases, B224BI-WH isolator bases, and B200S sounder bases. It also supports connection to the RA100Z remote LED annunciator.

The Notifier FSP-951T plug-in sensor head requires a separate mounting base wired directly into the two-wire fire alarm SLC loop:

  • Protocol Requirement: Compatible exclusively with fire alarm control panels running Notifier FlashScan protocol. Addressing is set manually on the detector head via two rotary decimal decade switches (01–159 on FlashScan loops).
  • Standard Detector Bases: B300-6 (white, 6-inch flanged base) and B501-WHITE (white, 4-inch standard European flangeless mounting base).
  • Functional Specialized Bases: B224RB-WH (relay base), B224BI-WH (isolator base), B200S-WH (addressable programmable sounder base), B200SR-WH (sounder base for retrofit applications), and B200S-LF-WH (520 Hz low-frequency sounder base for sleeping area requirements).
  • Backbox Specifications: Mounts to standard junction boxes with a required minimum depth of 1.5 inches (3.81 cm). Field wiring terminates via SEMS clamping plate screws.
  • Annunciation & Testing Accessories: Compatible with the RA100Z (3–32 VDC) remote LED annunciator when installed on B501 or B300-6 bases. Supports remote panel testing, FlashScan address-display walk testing, and local magnet testing via test magnets M02-04-00 or telescoping M02-09-00.