Answer:
The FSP-951T operates across an SLC loop voltage range of 15 to 32 VDC peak with an average standby current of 200 µA at 24 VDC and a maximum alarm current of 4.5 mA. It incorporates dual electronic thermistors calibrated to a 135°F (57°C) fixed-temperature threshold, has a height of 2.0 inches (51 mm), and weighs 3.4 oz (95 g).
The Notifier FSP-951T addressable multi-criteria smoke and heat detector provides integrated photoelectric obscuration sensing and thermal threshold detection designed for commercial fire alarm signaling circuits. Engineering specifications include:
- Operating Voltage: 15 to 32 VDC peak loop voltage across the two-wire Signaling Line Circuit (SLC).
- Standby Current: 200 µA maximum average at 24 VDC (one communication poll every 5 seconds with LED communication enabled).
- Maximum Alarm Current: 4.5 mA at 24 VDC with LED latched continuously red.
- Thermal Activation Setpoint: 135°F (57°C) fixed-temperature rating driven by dual electronic thermistors.
- Smoke Sensitivity: Factory preset at 1.5% nominal obscuration per foot, field programmable at the panel from 0.5% to 4.0% per foot obscuration.
- Air Velocity Rating: 0 to 4,000 ft/min (0 to 1,219.2 m/min) listed for open area and duct applications.
- Operating Environment: 32°F to 100°F (0°C to 38°C) temperature range; 10% to 93% relative humidity (non-condensing).
- Dimensions & Weight: 2.0" (51 mm) installed height; installed base diameter is 6.1" (15.6 cm) when paired with B300-6 series or 4.0" (10.2 cm) with B501 series bases. The detector sensor head shipping weight is 3.4 oz (95 g).