Notifier FSP-951T Installation and Commissioning Guidelines

Detachable Base Selection and Backbox Requirements

The Notifier FSP-951T intelligent plug-in smoke sensor mounts directly into a separate, detachable mounting base rather than terminating wiring directly onto the detector head. This architecture allows field technicians to complete rough-in wiring and verify circuit integrity before securing the sensor head. The detector head is compatible with several white base configurations, including the 6-inch B300-6 flanged base, the 4-inch B501-WHITE standard European flangeless base, the B224RB-WH relay base, the B224BI-WH isolator base, and the B200S-WH, B200SR-WH, and B200S-LF-WH addressable sounder bases.

For all base variants, mechanical mounting requires attachment to an electrical backbox with a minimum depth of 1.5 inches (3.81 cm) to ensure adequate clearance for loop cabling and junction terminations. Physical dimensions when mounted are dictated by the base: installed height is 2.0 inches (51 mm), while the installed diameter is 6.1 inches (15.6 cm) when paired with the B300-6 series and 4.0 inches (10.2 cm) when using the B501 series.

SLC Loop Wiring and Terminal Termination

Electrical connection to the Signaling Line Circuit (SLC) is established through SEMS terminal screws integrated into the detached base. Wiring must be installed in accordance with system design constraints:

  • Operating Voltage: Operates over an SLC line voltage range of 15 to 32 VDC peak.
  • Current Consumption: Maximum average standby current is 200 µA at 24 VDC (based on one communication every 5 seconds with LED activity enabled), with a maximum latched alarm current of 4.5 mA at 24 VDC.
  • Circuit Topology: Uses a two-wire SLC interface. Inherent supervision provided by the SLC protocol eliminates the need for end-of-line (EOL) resistors.
  • Branching: Wiring 'T-taps' or parallel branching runs are permitted exclusively on Class B SLC circuit layouts.
  • Annunciation Support: The base supports integration with the optional RA100Z remote LED annunciator (3 to 32 VDC) when using B501 or B300-6 mounting bases.

Rotary Decimal Addressing

Device identification on the SLC is configured locally using two integrated rotary decimal address switches located on the sensor assembly. Point ID capability allows the installer to set the exact decimal address without requiring specialized handheld electronic programmers. Address allocation must match the assigned device profile mapped in the fire alarm control panel configuration.

Ceiling Spacing, Airflow, and Environmental Constraints

Detector placement must follow NFPA 72 guidelines. In low airflow installations on smooth ceiling surfaces, spacing between adjacent detectors is recommended at a standard 30-foot (9.1 m) grid spacing. The detector mechanism is sealed against back pressure and features an insect-resistant screen with a removable fire-resistant plastic cover for field servicing.

The unit is UL/ULC listed for air velocities ranging from 0 to 4000 ft/min (0 to 1219.2 m/min), qualifying it for open-area protection as well as in-duct monitoring applications. Operating ambient temperature must remain between 32°F and 100°F (0°C to 38°C), with relative humidity maintained between 10% and 93% (non-condensing).

Commissioning and Field Functional Testing

Commissioning on Notifier FlashScan systems can be verified using the integrated walk test feature, which provides visual address feedback directly via the detector LEDs (for example, address 121 causes the LED to blink 12 times, pause, and then blink once). Initial functional testing can be performed on-site using an external test magnet (model M02-04-00 or telescoping handle model M02-09-00) placed adjacent to the unit's internal reed switch, or initiated remotely through control panel software commands.