Signaling Line Circuit (SLC) and Protocol Compatibility
The Notifier FSP-951T intelligent photoelectric smoke sensor operates exclusively using Notifier FlashScan protocol across a two-wire SLC loop. It is engineered for seamless communication with Notifier intelligent addressable fire alarm control panels configured for FlashScan transmission. Loop electrical characteristics require an operating voltage range of 15 to 32 VDC peak. Standby current consumption is rated at a maximum average of 200 µA at 24 VDC (based on one communication every 5 seconds with the LED blink enabled), with a peak alarm current of 4.5 mA at 24 VDC when the LED is continuously illuminated.
Addressing is established through two onboard rotary decimal address switches, providing discrete Point ID capability for each installed detector. Because the intelligent SLC loop provides inherent continuous supervision, external end-of-line resistors are not required. Wiring configurations support Class B branching and T-tappings without disrupting supervisory polling across the loop.
Compatible Mounting Bases
The FSP-951T detector head features a plug-in design terminating into a separate detachable mounting base secured via SEMS terminal screws. The detector is fully compatible with the following intelligent base options:
- B300-6: Standard white 6-inch (15.6 cm) diameter flanged mounting base, providing a complete installed profile height of 2.0 inches (51 mm).
- B501-WHITE: Compact white 4-inch (10.2 cm) diameter European-style flangeless mounting base.
- B224RB-WH: White addressable relay base designed for control of auxiliary emergency equipment.
- B224BI-WH: White isolator detector base designed to prevent short circuits from disabling an entire SLC loop.
- B200S-WH: White intelligent addressable sounder base capable of synchronized audible notification.
- B200SR-WH: White intelligent sounder base for standard tone signaling.
- B200S-LF-WH: White low-frequency sounder base designed to meet specialized acoustic signaling criteria.
Peripheral Accessories and Enclosure Fitment
When installed on either the B501 or B300-6 base platforms, the FSP-951T supports the Notifier RA100Z remote LED annunciator. The RA100Z operates across a 3 to 32 VDC supply range and mounts directly onto a standard U.S. single-gang electrical enclosure to indicate active alarm status outside closed rooms or concealed spaces.
Physical backbox installations require a minimum junction box depth of 1.5 inches (3.81 cm) to accommodate wiring and SEMS terminal clearance across all compatible base styles. For functional walk-testing and maintenance, the sensor is compatible with the M02-04-00 handheld test magnet and the M02-09-00 test magnet equipped with a telescoping handle.
Legacy Migration and Environmental Ratings
The FSP-951T serves as a direct functional replacement for legacy Notifier FSP-851 Series addressable smoke detectors on FlashScan loops, allowing straightforward head replacement without altering existing field base wiring. The sensor is rated for air velocities from 0 to 4000 ft/min (0 to 1219.2 m/min), certifying compatibility with both open ceiling installations and in-duct sampling applications within relative humidity ranges of 10% to 93% non-condensing.