Answer:
The GST DI-9204E operates on a 24 VDC loop voltage (16 VDC to 28 VDC) with a standby current of ≤0.6 mA and alarm current of ≤1.8 mA. Its dimensions are 87.1 mm × 87.1 mm × 58.5 mm with the back box (87.1 mm × 87.1 mm × 23.5 mm without back box) with an IP43 ingress protection rating.
The GST DI-9204E Digital Manual Call Point is an addressable initiating device engineered for commercial and industrial fire alarm networks. Its technical, electrical, and physical specifications include:
- Operating Voltage: 24 VDC loop voltage (operating range 16 VDC to 28 VDC).
- Current Consumption: Standby current consumption is ≤0.6 mA; active alarm current consumption is ≤1.8 mA.
- Dimensions: 87.1 mm (L) × 87.1 mm (W) × 58.5 mm (H) when mounted with the surface back box, and 87.1 mm × 87.1 mm × 23.5 mm when semi-flush mounted without the back box.
- Weight: Approximately 160 g with the back box, and approximately 107 g without the back box.
- Mounting Hole Spacing: Standard 60 mm hole pitch distance.
- Environmental Limits: Operating temperature range from -10°C to +55°C, with relative humidity handling up to 95% non-condensing.
- Ingress Protection: Rated IP43 for Type A indoor installation.