Answer:
The GST I-9301 is fully compatible with GST intelligent addressable fire control panels, including GST 200, GST 200-2, GST 5000, GST 9000, and GST-IFP8. It installs onto standard single-gang electrical back boxes with 6.5 cm mounting hole spacing or the GST B-9310 surface back box, and addresses via GST P-9910 and P-9910B handheld programmers.
Compatibility for the GST I-9301 single I/O module spans control panels, field programming instruments, and physical mounting accessories:
- Fire Alarm Control Panels: Fully compatible with the GST intelligent protocol used across GST 200, GST 200-2, GST 5000, GST 9000, and GST-IFP8 addressable panels.
- Handheld Programmers: Field addressing (range 1–242) and mode selection (two-wire or four-wire) are set via GST P-9910 or P-9910B handheld programmers connected directly to terminals Z1 and Z2.
- Mounting Hardware: Features a plug-in two-part base assembly. Compatible with standard flush single-gang junction boxes featuring 6.5 cm mounting hole spacing, as well as the surface-mount GST B-9310 conduit back box.
- Output Peripherals: Capable of driving external building management shutdown contacts or powering conventional notification appliances such as the GST C-9403 conventional sounder strobe.
- Field Cabling: Requires minimum 1.0 mm² fire-resistant cable for non-polarized loop lines (Z1/Z2) and minimum 1.5 mm² fire-resistant cable for 24VDC auxiliary power supply connections (D1/D2).