Answer:
The GST I-9301 operates at 24VDC (nominal range 16VDC to 28VDC) with a loop standby current of 1mA and an alarm action current of 5mA. It measures 120 mm x 80 mm x 39 mm with a net weight of 0.12 kg, houses an IP30-rated ABS casing in ivory white, and provides passive relay switching capacity of 5A at 24VDC (3A at 110VAC) or an active output of 24VDC at 1A.
The GST I-9301 Addressable Single Input/Output Module is engineered for fire alarm plant control and signaling circuits. Key technical specifications include:
- Operating Voltage: 24VDC loop voltage (operating range 16VDC to 28VDC); power supply input voltage 24VDC (16VDC to 28VDC).
- Operating Current: Loop standby current of ≤ 1mA; alarm action current of ≤ 5mA.
- Output Capacity: Passive volt-free relay contacts rated at 5A at 24VDC (or 3A at 110VAC); active supervised output rated at 24VDC at 1A.
- Physical Dimensions & Weight: 120 mm (L) × 80 mm (W) × 39 mm (H); net bare unit weight of 0.12 kg.
- Housing & Ingress Protection: ABS plastic construction in ivory white finish with an IP30 protection rating.
- Environmental Limits: Operating ambient temperature range from -10°C to +50°C (up to +55°C per ambient enclosure testing) with relative humidity up to 93% non-condensing.
- Addressing: Electronic addressing occupying 1 address on the detection loop within the 1 to 242 range.