Back to Product
Compatibility

Hardware and System Compatibility

Master Multi-Door Controller Compatibility

The eSSL FR1200 is engineered specifically as a slave biometric exit reader that operates in conjunction with an upstream master host. It communicates via an RS-485 serial interface to eSSL inBio series multi-door access control panels, including the inBio 160, inBio 260, and inBio 460 / 460 Pro systems. In this configuration, the FR1200 captures fingerprint scans and RFID card reads, transmitting raw credential data over the serial connection directly to the control panel.

Because template storage, verification algorithms, and access logic reside entirely on the inBio controller, user fingerprints do not need to be re-enrolled or registered on the FR1200 itself. If a slave unit is swapped or replaced during field maintenance, existing fingerprint templates and access levels remain intact in the central panel database.

Standalone Master Biometric Terminal Integration

In addition to centralized multi-door control panels, the FR1200 connects directly to compatible eSSL standalone biometric terminals across an RS-485 bus. Supported standalone master terminal models include the eSSL X990, F18, F19, F22, and SF100. In these deployments, the standalone unit acts as the primary master reader for door entry, while the FR1200 serves as the egress reader to enforce bidirectional biometric tracking and anti-passback controls.

Credential verification for exit events is executed against the biometric templates stored in the master terminal. Standalone terminals process the transaction and log the corresponding IN/OUT event records for access control and time-attendance reporting without requiring local template storage on the FR1200.

RS-485 Bus Architecture and Hardware Addressing

Integration of the FR1200 into RS-485 networks requires hardware-level addressing using the reader's integrated DIP switches. Installers must assign a unique RS-485 device address to each FR1200 on the bus to establish its door number and reader position (entry or exit). Misconfigured DIP switches or duplicate addresses will cause communication drops between the slave reader and the host controller.

RS-485 polarity must be maintained across the entire installation; reversing the 485+ and 485- polarities prevents data transmission. For long-distance RS-485 serial communication runs reaching up to 100 meters, a 120-ohm terminal resistance must be connected across the 485+ and 485- lines at the end of the bus to ensure signal integrity.

Power Supply and Line Length Requirements

The FR1200 operates on a 12V DC power supply, drawing less than 100 mA in standby mode and a maximum current of less than 120 mA during active read cycles. When powered directly through an inBio controller's EXT485 auxiliary bus, the aggregate current consumption of all connected RS-485 devices must remain below the 500 mA maximum limit. If cable distances exceed 100 meters or the current threshold is exceeded, a separate external 12V DC power supply must be installed adjacent to the reader.

RFID Credential Format Support

The FR1200 features an optical biometric sensor and is available with factory-integrated RFID reader modules. Supported credential technologies include standard Proximity (ID, 125 kHz), MIFARE (13.56 MHz), and HID card formats, ensuring direct card format parity with the host master terminal or inBio access system.

Compatible Master HardwareInterface ProtocolSystem RoleTemplate Verification Handling
eSSL inBio 160 / 260 / 460 / 460 ProRS-485 SerialMulti-Door Access ControllerExecuted centrally on inBio control panel
eSSL F18 / F19 / F22RS-485 SerialMaster Standalone TerminalExecuted directly on master terminal
eSSL X990RS-485 SerialMaster Biometric TerminalExecuted directly on master terminal
eSSL SF100RS-485 SerialMaster Standalone TerminalExecuted directly on master terminal