Back to Product
FAQ

What are the key technical and enclosure specifications of the Honeywell Morley-IAS DXc4 panel?

Answer:
The Honeywell Morley-IAS DXc4 (714-001-241) is a 4-loop addressable fire alarm control panel measuring 391.5 x 390 x 147 mm and weighing 4.5 kg without standby batteries (they are not included). It operates on 110/230V AC (±15%), incorporates an internal 24V DC 4A power supply unit, delivers 500mA driver capacity per loop, and provides 2 monitored 1A sounder circuits alongside 3 auxiliary relays.

The Honeywell Morley-IAS DXc4 (manufacturer part number 714-001-241) is an analogue addressable fire alarm control panel designed for commercial, industrial, and institutional premises. Built into an IP30-rated enclosure featuring a mild steel rear chassis and an ABS plastic front cover (BS EN 60950) finished in RAL 9002 Grey white, the panel measures 391.5 mm (H) × 390 mm (W) × 147 mm (D) and weighs 4.5 kg excluding standby batteries (they are not included).

Key technical and electrical specifications include:

  • Loop Capacity: 4 addressable detection loops with a 500mA multi-protocol loop driver per loop.
  • Power Input & PSU: 110V / 230V AC ±15% (50/60 Hz) operating supply backed by an internal EN 54-4 compliant 24V DC 4A power supply unit.
  • Sounder & Auxiliary Outputs: 2 independent monitored sounder circuits rated at 1A per circuit, alongside one fused auxiliary DC supply output delivering +24V DC at 250mA.
  • Relays & Inputs: 3 onboard single-pole changeover relays rated at 24V DC 1A (Fire relay, Fault/Extended Fire Transmission relay, and a programmable Aux relay), plus 2 onboard monitored inputs.
  • Display & Controls: 6 × 40 character (240 × 64 pixels) blue backlit LCD, 12-key alphanumeric programming keypad, navigation arrows, system control pushbuttons, and support for up to 160 software fire zones.
  • Cable Management: 29 knockouts of 20 mm diameter (25 knockouts on the top face and 4 on the bottom face) with plug-in screw terminal block connectors.