Back to Product
FAQ

What are the electrical ratings and display specifications of the Notifier LCD-160 annunciator?

Answer:
The Notifier LCD-160 features a 640-character backlit display (40 characters wide by 16 lines deep) operating on a regulated, filtered 24 VDC non-resettable power supply. It draws 0.300 A in standby (0.075 A with backlight off) and 0.325 A in alarm mode, with a total shipping weight of 2.50 lb (1.134 kg).

The Notifier LCD-160 liquid crystal display annunciator provides a 640-character viewing area arranged across 40 characters wide by 16 lines deep with backlit control, occupying two standard ACS annunciator module locations. It mimics the top 160 characters of the host NFS-3030 or NFS2-3030 panel to display live event data and preprogrammed custom messages.

Key electrical, wiring, and operating specifications include:

  • Input Supply Voltage (TB2): Regulated, filtered 24 VDC via a non-resettable power supply interface listed for fire-protective signaling use.
  • Current Consumption: Standby current is 0.300 A with backlight enabled and 0.075 A with backlight deactivated. Alarm current is 0.325 A with backlight illuminated and all status LEDs active.
  • RDP Serial Bus Communication: Supervised, power-limited interface connecting via 18 to 12 AWG (0.78 to 3.1 mm²) twisted-pair cable with a characteristic impedance of 120 ohms ± 20%. Supports distances up to 4,000 feet (1,219.2 m) at 18 AWG.
  • Loop Limits: Maximum circuit resistance must not exceed 100 ohms across the RDP bus and 10 ohms on the 24 VDC power circuit. Resistance between unloaded RDP connectors must measure greater than 1,000 ohms.
  • Operating Environment & Dimensions: Rated across 0°C to 49°C (32°F to 120°F) at 93% ± 2% RH non-condensing at 32°C ± 2°C (90°F ± 3°F). Shipping weight is 2.50 lb (1.134 kg).