Notifier LCD-160 Installation and Field Wiring Guidelines

The Notifier LCD-160 annunciator connects to NOTIFIER NFS-3030 and NFS2-3030 Fire Alarm Control Panels (FACPs) via a supervised Remote Data Port (RDP) communications circuit and a dedicated 24 VDC operating power feed. Designed to fit into two standard ACS annunciator module locations, the unit can be housed remotely in specialized backboxes or integrated directly into panel enclosures. Adhering to manufacturer electrical and routing limits ensures stable remote telemetry and command center performance.

RDP Bus Wiring and Distance Limits

The supervised, power-limited Remote Data Port interface connects to the terminal block TB1. The RDP serial circuit supports up to 32 RDP devices on a single run. The FACP host panel must sit at one physical end of the bus, while the last RDP device on the run must have an enabled end-of-line termination resistor.

  • Conductor Gauge: 18 AWG to 12 AWG (0.78 mm² to 3.1 mm²) twisted-pair cable.
  • Cable Impedance: 120 ohms ± 20% characteristic impedance.
  • Maximum Loop Distance: Up to 4000 feet (1219.2 m) when utilizing 18 AWG (0.78 mm²) twisted-pair cable.
  • Bus Resistance Limit: Maximum 100 ohms total wire resistance across the RDP circuit.
  • Unloaded Resistance: Electrical resistance measured between unloaded RDP connector terminals must measure greater than 1k ohm.

Power Circuit Requirements (TB2)

The annunciator draws operating current via terminal block TB2 from a non-resettable, regulated, filtered 24 VDC source listed for fire-protective signaling. Supply options include panel auxiliary outputs, AMPS-24 main power supplies, APS2-6R auxiliary power supplies, or compatible listed signaling accessory outputs. Current demand varies by operating state: 0.075 A in standby with display backlight turned off, 0.300 A in standby with backlight on, and 0.325 A during alarm conditions with the backlight illuminated and all visual status LEDs active.

Total wiring resistance on the 24 VDC power circuit must remain below 10 ohms. If wire loop calculations show total resistance exceeding 10 ohms, install a dedicated remote power supply near the annunciator location. When multiple RDP devices on the loop utilize separate external power supplies, a common electrical reference connection must be interconnected between all supplies. A drop or loss of 24 VDC operating power is inherently supervised across the system and reports as a communication failure at the central NFS-3030/NFS2-3030 control panel.

Conduit Separation and Electrical Noise Isolation

To avoid signal degradation and transient noise coupling, observe strict field wiring isolation guidelines:

  • Do not route RDP communication conductors adjacent to or within the same conduit as 120 VAC electrical service lines.
  • Keep the serial data circuit isolated from high-noise electrical lines powering mechanical horns or vibrating bells.
  • Avoid running parallel conduits or shared raceways with motor control circuits, SCR power feeds, audio circuits exceeding 25 Vrms, or any non-power-limited circuits.
  • When 24 VDC operating power is provided by a non-power-limited power source, it must maintain physical separation from the power-limited RDP communication circuit.

Enclosure and Mounting Options

The physical chassis of the LCD-160 occupies two ACS annunciator positions and supports several certified enclosure configurations:

  • ABS-2D(C) / ABS-2DR: Black or red remote surface/semi-flush enclosures. Box dimensions measure 12.0" H x 12.0" W x 3.797" D (30.480 cm x 30.480 cm x 9.644 cm), with a door depth of 1.250" D (3.175 cm). Note that the optional AKS-1B key switch cannot be mounted within ABS-2D or ABS-2DR enclosures.
  • ABS-4D(C) / ABS-4DR: Multi-module surface/semi-flush enclosures (box dimensions: 11.97" H x 19.87" W x 3.5" D) designed to mount one LCD-160 along with two additional annunciator modules directly on a hinged dress plate. The AKS-1B key switch cannot be mounted in ABS-4D or ABS-4DR backboxes.
  • CAB-4 Series Cabinets: For local panel integration, the LCD-160 mounts to the top tier of CAB-4 Series enclosures using a hinged DP-DISP dress panel display, or via the black ADP-4B annunciator dress panel (paired with an optional VP-2B vented dress panel). CAB-4 cabinets accommodate one to four rows of equipment plus batteries (they are not included), fitting up to two 26 AH batteries (they are not included).

Diagnostics and Commissioning Checks

During initial system power-up, verification can be performed using both internal and external status indicators. Four internal diagnostic LEDs assist installation engineers: Status LED11 (green) blinks upon valid power, Receive LED12 (green) blinks when incoming serial data packets arrive from the RDP line, Transmit LED13 (green) blinks during response transmissions, and Microfail LED14 (yellow) illuminates only if the onboard microcontroller encounters an operating fault. Executing the front-panel Lamp Test verifies the integral piezo sounder, lights all visual LED indicators, and outputs active firmware revision levels directly to the 640-character display without requiring physical chip replacement.