Back to Product
Compatibility

System and Hardware Compatibility

Fire Alarm Control Panel Integration

The NOTIFIER LCD-160 remote annunciator is engineered specifically for direct integration with the NOTIFIER NFS-3030 and NFS2-3030 intelligent addressable Fire Alarm Control Panels (FACPs). The unit functions as an exact operational extension of the host system, mimicking the top 160 characters of the panel's native 640-character liquid crystal display to present real-time alarm, supervisory, trouble, and preprogrammed status text. For Canadian regulatory jurisdictions, the ULC-listed counterpart is designated as model LCD-160C.

Full Display and Control Center (DCC) capability is supported between the LCD-160 and host panels. This architecture allows network control authority to pass between alternate operating centers, featuring a standardized 15-second automatic timeout protocol to facilitate seamless command handoff during event acknowledgment, signal silence, system reset, and drill sequences.

Power Supply Interface & Compatibility

The LCD-160 requires an operating input voltage across terminal TB2 of filtered, regulated 24 VDC supplied from a non-resettable power source listed for fire-protective signaling applications. The annunciator draws 0.300 A in standby with the backlight illuminated, 0.075 A in standby with the backlight turned off, and 0.325 A under full alarm conditions with the backlight active and all status LEDs energized. Compatible power sources include:

  • Host FACP integrated non-resettable 24 VDC auxiliary power outputs
  • NOTIFIER AMPS-24 main addressable power supplies
  • NOTIFIER APS2-6R auxiliary power supplies
  • Listed 24 VDC fire alarm accessory power supply outputs

The 24 VDC circuit must maintain a maximum series loop resistance of no more than 10 ohms. If the total wire resistance to the LCD-160 exceeds 10 ohms, a dedicated remote power supply must be installed. When multiple devices across the bus are powered by distinct power supplies, a common electrical reference must be connected between all supplies. Total loss of DC input voltage is inherently supervised via the bus and registers at the panel as a communication fault.

RDP Communication Bus Specifications

Serial data communications are handled through terminal TB1 via the proprietary NOTIFIER Remote Data Port (RDP) supervised, power-limited serial interface. Electrical and network limits include:

  • Capacity: A single RDP bus supports up to 32 compatible RDP devices, with the host FACP positioned at one end of the bus and an enabled end-of-line resistor placed across the final physical device.
  • Cabling Media: High-integrity twisted-pair cable rated from 18 AWG to 12 AWG (0.78 mm² to 3.1 mm²) possessing a nominal characteristic impedance of 120 ohms ± 20%.
  • Bus Distance: Maximum wire run reaches up to 4000 feet (1219.2 m) when utilizing 18 AWG (0.78 mm²) cable.
  • Electrical Resistance: Total circuit resistance along the RDP bus must not exceed 100 ohms, and unloaded electrical resistance across open RDP connectors must measure greater than 1k ohm.

Enclosure, Dress Panel & Cabinet Hardware Compatibility

The physical footprint of the LCD-160 is designed to occupy exactly two standard ACS annunciator module positions. The annunciator integrates into several standardized NOTIFIER enclosures and dress plates:

  • ABS-2D(C) / ABS-2DR: Black or red remote surface/semi-flush enclosures. Box dimensions measure 12.0" H x 12.0" W x 3.797" D (30.48 cm x 30.48 cm x 9.64 cm) with door dimensions of 12.0" H x 12.0" W x 1.250" D (30.48 cm x 30.48 cm x 3.18 cm).
  • ABS-4D(C) / ABS-4DR: Multi-module surface/semi-flush remote enclosures finished in black or red, accommodating one LCD-160 alongside two additional annunciator modules on a hinged dress plate (backbox dimensions: 11.97" H x 19.87" W x 3.5" D [30.40 cm x 50.47 cm x 8.89 cm]).
  • CAB-4 Series Cabinets: Compatible with single- to four-row system cabinets accommodating operational hardware and system standby batteries (they are not included) (up to two 26 AH batteries (they are not included)).
  • DP-DISP Dress Panel: Hinge-mounted display plate designed for installing the LCD-160 directly into the top tier of any CAB-4 Series cabinet.
  • ADP-4B & VP-2B: Annunciator Dress Panel-4B (black) designed for CAB-4 cabinet rows, with optional VP-2B vented dress panel integration.

Accessory Integration & Key Switch Constraints

Physical access security for the LCD-160 rubberized membrane keys is supported via an optional AKS-1B Annunciator Key Switch connected directly to the unit's dedicated key switch input terminals. System designers must note mounting limitations: the AKS-1B key switch cannot be mechanically accommodated inside the ABS-1B, ABS-2D, ABS-2DR, ABS-4D, or ABS-4DR enclosure assemblies, requiring external enclosure configuration or standard CAB-4 dress plate installations when keyed security is mandatory.