Back to Product
FAQ

What panels, backboxes, and hardware accessories are compatible with the Notifier FCM-1?

Answer:
The FCM-1 is compatible with Notifier intelligent addressable fire alarm control panels running FlashScan or CLIP protocols. It mounts inside a standard 4-inch square electrical box with a minimum depth of 2.125 inches or the optional SMB500 surface-mount box, and works with the CB500 electrical barrier and A2143-20 audio capacitor.

Hardware and system compatibility for the Notifier FCM-1 includes:

  • Control Panels: Operates on intelligent Notifier fire alarm control panels using either FlashScan protocol (address range 01–159) or Classic Loop Interface Protocol (CLIP, address range 01–99). Internal logic automatically transmits its device type code to the panel.
  • Junction Boxes: Installs directly onto a standard 4-inch (101.6 mm) square electrical box with a minimum required depth of 2.125 inches (53.975 mm). Alternatively, it can be mounted using the Notifier SMB500 surface-mount electrical backbox.
  • CB500 Barrier: UL installation standards mandate the use of the CB500 control module barrier when separating power-limited and non-power-limited wiring within the same junction box enclosure.
  • Audio Capacitor: Class A (Style Z) speaker evacuation installations require the optional Notifier A2143-20 capacitor accessory.