Answer:
The FCM-1 provides a supervised Notification Appliance Circuit (NAC) output to power and monitor external 24 VDC notification appliances or 70.7 Vrms speakers. In contrast, the FRM-1 provides two unpowered Form-C dry relay contacts that switch together for auxiliary equipment control without circuit supervision.
While both modules share the same physical footprint, FlashScan rotary addressing, and 15 to 32 VDC loop operating range, their switching functionality differs significantly:
- Notifier FCM-1 (Control Module): Designed specifically to supervise and activate notification circuits. It switches external power (24 VDC regulated or 70.7 Vrms / 50 W audio) to audible and visual notification appliances (horns, strobes, speakers). It actively monitors field wiring for open, normal, and short conditions.
- Notifier FRM-1 (Relay Module): Designed for auxiliary dry-contact switching. It incorporates two Form-C contacts that switch simultaneously without providing line supervision. It is rated for loads such as 3 A at 30 VDC resistive or 0.9 A at 120 VDC/VAC, making it suitable for fan shutdowns, damper actuation, door holder releases, and four-wire smoke detector power reset rather than supervised notification appliance circuits.