Notifier FCM-1 Installation and Wiring Guidelines

Backbox Mounting and Mechanical Enclosure

The Notifier FCM-1 addressable control module is engineered to mount directly into standard field enclosures. It fits a standard 4-inch (101.6 mm) square electrical junction box with a minimum depth of 2.125 inches (53.975 mm). For installations requiring surface routing, the unit can be housed inside the optional Notifier SMB500 surface-mount electrical box.

The module features an off-white heat-resistant plastic face plate with external dimensions of 4.5 inches (114.3 mm) in height, 4 inches (101.6 mm) in width, and 1.25 inches (31.75 mm) in depth. Detailed installation mechanical layouts and screw torque requirements should be verified using Notifier document I56-1169.

Rotary Decimal Address Configuration

Field addressing is completed before mounting the module into the electrical backbox. Two integrated rotary decimal switches on the front face allow direct-dial entry of the module address without requiring specialized handheld programmers:

  • FlashScan Protocol: Direct-dial setting from address 01 to 159.
  • CLIP (Classic Loop Interface Protocol): Direct-dial setting from address 01 to 99.

Each address must be uniquely allocated on the Signaling Line Circuit (SLC) loop. When commissioning releasing service systems, refer to Notifier SLC Manual PN 51253 for specific address allocation and panel configuration parameters.

Field Wiring and Circuit Supervision

Electrical connections are made via heavy-duty SEMS screws fitted with integral clamping plates to secure bare field wiring. The FCM-1 module controls a single field circuit configured as either Class B (Style Y) or Class A (Style Z) wiring:

  • Class B (Style Y) Installations: Rated for a maximum continuous output current of 3 A.
  • Class A (Style Z) Installations: Rated for a maximum continuous output current of 2 A.
  • Speaker Circuits: When wiring high-level 70.7 Vrms audio circuits in a Class A (Style Z) topology, the optional A2143-20 capacitor accessory is mandatory for circuit operation.

The maximum permissible voltage drop across the notification appliance circuit (NAC) wiring run is 4 VDC. The FCM-1 monitors the supervised notification circuit and reports open, normal, and short circuit line conditions back to the intelligent fire alarm control panel.

External Power Supply and CB500 Barrier Separation

The FCM-1 internal logic and relay coil operate directly from the two-wire SLC loop (15 to 32 VDC). Operating load power is connected across terminals T10 and T11 from an external source:

  • Audible/Visual NAC Devices: External regulated 24 VDC maximum supply with a maximum supervisory standby drain of 1.7 mA.
  • Audio Speaker Circuits: Maximum 70.7 V RMS, 50 W audio signal source with a maximum supervisory standby drain of 2.2 mA (evaluated at 80 VRMS).

The external supply is relay-isolated from the primary communication SLC loop, ensuring that an external power supply fault or short cannot compromise SLC communications. Under UL standards, whenever power-limited wiring and non-power-limited wiring share the same electrical junction box with the FCM-1, the UL-required CB500 Control Module Barrier must be installed to maintain physical circuit separation.

Environmental Verification and Initial Diagnostics

Prior to commissioning, confirm that the installation environment remains within the manufacturer operating temperature limit of 32°F to 120°F (0°C to 49°C) and a relative humidity range of 10% to 93% non-condensing.

Upon loop power-up, observe the integrated wide-viewing-angle status LED. The LED blinks green during normal direct or group polling communication from the fire alarm control panel. When the output circuit activates, the LED transitions to steady red. If silent operation is specified for the facility, green polling blinks can be disabled globally at the panel.