What are the electrical ratings and physical dimensions of the Honeywell Morley HM-MCP-GLASS call point?

Answer:
The HM-MCP-GLASS operates on a 15 V DC to 32 V DC loop supply with an 80 µA standby current and 130 µA alarm current at 24 V DC. In semi-flush mounting configuration, it measures 89 mm (W) x 93 mm (H) x 27.5 mm (D) and weighs approximately 110 g to 130 g.

The Honeywell Morley-IAS HM-MCP-GLASS analogue addressable manual call point is built to the following technical and physical specifications:

  • Operating Voltage Range: 15 V DC to 32 V DC maximum loop power
  • Quiescent Current: 80 µA at 24 V DC (standby, without active communication)
  • Alarm Current: 130 µA at 24 V DC (with active communication)
  • Semi-Flush Dimensions: 89 mm (W) x 93 mm (H) x 27.5 mm (D)
  • Surface Mount Dimensions: 89 mm (W) x 93 mm (H) x 59.5 mm (D)
  • Weight: 110 g to 130 g (semi-flush mount); 180 g (surface mount with standard back box)
  • Ingress Protection: IP24D
  • Operating Temperature: -10°C to 55°C
  • Relative Humidity: 10% to 93% non-condensing