Answer:
The HM-MCP-GLASS operates on a 15 V DC to 32 V DC loop supply with an 80 µA standby current and 130 µA alarm current at 24 V DC. In semi-flush mounting configuration, it measures 89 mm (W) x 93 mm (H) x 27.5 mm (D) and weighs approximately 110 g to 130 g.
The Honeywell Morley-IAS HM-MCP-GLASS analogue addressable manual call point is built to the following technical and physical specifications:
- Operating Voltage Range: 15 V DC to 32 V DC maximum loop power
- Quiescent Current: 80 µA at 24 V DC (standby, without active communication)
- Alarm Current: 130 µA at 24 V DC (with active communication)
- Semi-Flush Dimensions: 89 mm (W) x 93 mm (H) x 27.5 mm (D)
- Surface Mount Dimensions: 89 mm (W) x 93 mm (H) x 59.5 mm (D)
- Weight: 110 g to 130 g (semi-flush mount); 180 g (surface mount with standard back box)
- Ingress Protection: IP24D
- Operating Temperature: -10°C to 55°C
- Relative Humidity: 10% to 93% non-condensing