Back to Product
FAQ

What are the electrical ratings, dimensions, and operating limits of the Honeywell HM-PTSE-AP detector?

Answer:
Installed in its standard B501AP base, the HM-PTSE-AP measures 61 mm in height and 102 mm in diameter, with a total weight of 99 g. It operates on an addressable loop voltage of 15 to 32 V DC, drawing a standby current of 200 µA at 24 V DC (300 µA with LED pulse enabled) within an operating temperature range of -30°C to +70°C.

The Honeywell Morley-IAS HM-PTSE-AP multi-criteria detector delivers precise electrical and mechanical characteristics designed for loop-powered commercial addressable systems:

  • Operating Voltage: 15 to 32 V DC (non-isolated).
  • Standby Current: 200 µA @ 24 V DC without communication; 300 µA @ 24 V DC when LED blink is configured every 5 seconds.
  • Alarm Current: 3.5 mA @ 24 V DC (with dual red LEDs activated).
  • Remote Output Capability: 22.5 V DC at 10.8 mA maximum.
  • Dimensions: 61 mm (height) × 102 mm (diameter) when seated in the standard B501AP base.
  • Total Weight: 99 g including the mounting base.
  • Enclosure Material: PC/ABS polymer housing.
  • Environmental Limits: Operating temperature range from -30°C to +70°C (with normal ambient not exceeding 50°C), and relative humidity from 10% to 93% (non-condensing).