Answer:
The HM-PSE-S2 requires a Honeywell Morley-IAS B501AP plug-in base (supporting wire gauges up to 2.5 mm²) and connects directly to Morley-IAS addressable fire alarm control panels, including DXc, ZX, and PL series systems.
The Honeywell HM-PSE-S2 is designed for addressable loop architectures across Morley-IAS fire detection infrastructures:
- Mounting Base: Plugs directly into the Morley-IAS B501AP addressable base. The base terminals accommodate solid or stranded field wiring up to a maximum wire gauge of 2.5 mm².
- Loop Addressing: Manual channel addressing is set directly on the detector body using two integrated rotary decade switches (01–99 address range).
- Control Panel Compatibility: Fully compatible with Honeywell Morley-IAS intelligent addressable fire alarm control panels, such as the PL-1000, DXc, and ZX product lines.
- Remote Annunciator Support: Features dedicated remote indicator outputs to operate external visual indicators at 22.5 V DC (10.8 mA maximum).
- Status Monitoring: Fitted with dual 360-degree viewing LEDs that provide immediate visual status confirmation from any approach angle.