Answer:
The Honeywell HM-PSE-S2 operates on 15 to 32 V DC, drawing 200 µA in standby (300 µA with LED blink) and 3.5 mA in alarm state at 24 V DC. Installed in its B501AP base, it measures 52 mm in height, 102 mm in diameter, and weighs 97 g.
The Honeywell Morley-IAS HM-PSE-S2 addressable photoelectric smoke detector features precise electrical, operational, and dimensional specifications for commercial and industrial fire alarm loops:
- Operating Voltage Range: 15 V DC to 32 V DC
- Standby Current: 200 µA at 24 V DC without communications; 300 µA at 24 V DC with LED blink active every 5 seconds
- Alarm Current: 3.5 mA at 24 V DC (red alarm LED illuminated)
- Remote Output: 22.5 V DC output voltage at 24 V DC loop supply, supporting up to 10.8 mA maximum current
- Loop Resistance: Introduces typically 20 mΩ (maximum 30 mΩ) additional loop resistance when used with the B501AP base
- Installed Dimensions: 52 mm (height) × 102 mm (diameter) when mounted inside the standard B501AP base
- Weight: 97 g including base (individual shipping weight 0.12 kg)
- Operating Environment: Rated for ambient temperatures from -30°C to +70°C and relative humidity levels between 10% and 93% (non-condensing)
- Housing Construction: Manufactured from ivory-colored PC/ABS blend