What are the electrical ratings, loop capacity, and physical dimensions of the Honeywell Morley-IAS DXc2 panel?

Answer:
The DXc2 measures 391.5 x 390 x 147 mm (H x W x D) and operates on 230 V AC (50/60 Hz). It provides 2 analogue addressable loops rated up to 500 mA each, 2 monitored sounder circuits rated at 1 A each, and space inside the housing for two 12 V / 17 Ah backup batteries (they are not included).

The Honeywell Morley-IAS DXc2 (Ref: KTI07001001DXC2 / Part Number 714-001-221) is an analogue addressable fire alarm control panel built into an IP30-rated enclosure measuring 391.5 mm high, 390 mm wide, and 147 mm deep. The enclosure combines a mild steel rear chassis with an ABS plastic front cover conforming to BS EN 60950, finished in gray-white (similar to RAL 9002). For cable entry, the enclosure provides 25 knock-outs (20 mm) at the top and 2 knock-outs (20 mm) at the bottom.

Key electrical and hardware specifications include:

  • Mains Operating Voltage: 230 V AC (+15%, -15% tolerance) at 50/60 Hz.
  • Addressable Detection Loops: 2 analogue addressable loops with a maximum current loading of 500 mA per loop.
  • Sounder Circuits: 2 monitored onboard sounder outputs, each rated up to 1 A.
  • Auxiliary Output: 24 V DC / 250 mA (fused/resettable) auxiliary supply for field interfaces.
  • Zone Capacity: Up to 160 software-defined fire zones.
  • Relays: Onboard volt-free relays for Fire, Fault, and Auxiliary programmable signaling.
  • Display: 6 x 40 character (240 x 64 pixels) blue backlit liquid crystal display (LCD).
  • Standby Power: Battery compartment engineered to house up to 2 x 12 V / 17 Ah sealed lead-acid batteries (they are not included).
  • Operating Environment: 0°C to 40°C ambient temperature with 5% to 95% non-condensing relative humidity.