Answer:
The GST I-9104 connects directly to addressable GST Fire Alarm Control Panels (FACP) over a 2-wire non-polarized loop using 1.0 mm² or larger copper-core cable. It mounts onto the GST DZ-03 Common Detector Base and is electronically addressed and configured using the GST P-9910B Hand Held Programmer.
System hardware compatibility and installation requirements for the GST I-9104 detector include:
- Fire Alarm Control Panels: Connects directly to GST addressable FACPs, which continually poll the detector and report fire and fault data.
- Mounting Base: Installs on the GST DZ-03 Common Detector Base (ordered separately). The base accommodates back box mounting screw spacings from 45 mm to 75 mm, and the detector locks into place with a clockwise rotation.
- Loop Cabling: Requires a 2-wire non-polarized connection connected to diagonal base terminals using copper-core cable of 1.0 mm² or greater cross-sectional area.
- Electronic Programming: Electronic addressing supports an address range from 1 to 242. Sensitivity level adjustments and address assignments are configured using the GST P-9910B Hand Held Programmer.