Answer:
The NFS2-640E supports Notifier FlashScan addressable detectors (such as FSP-951, FST-951, FSV-951), control and monitor modules (FMM-1, FCM-1, FRM-1, NBG-12LX), and the FWSG SWIFT wireless gateway. It also connects up to 32 remote annunciators (such as FDU-80 and LCD2-80) and integrates into NOTI-FIRE-NET networks up to 200 nodes.
The Notifier NFS2-640E integrates with a wide selection of ONYX Series field hardware, peripheral modules, and network topologies:
- FlashScan Detectors: Compatible with photoelectric (FSP-951), thermal (FST-951), multi-criteria (FCO-951, FPTI-951), high-sensitivity VIEW (FSV-951), and linear beam smoke detectors (FS-OSI-RI).
- Addressable Modules: Interfaces with manual pull stations (NBG-12LX), monitor modules (FMM-1), control modules (FCM-1), relay modules (FRM-1), multi-circuit modules (XP6/10 series), and 4–20 mA gas sensing modules (FMM-4-20).
- Wireless Integration: Connects to SWIFT Smart Wireless Integrated Fire Technology via the FWSG wireless gateway, accommodating up to 49 wireless field devices per gateway with up to 4 overlapping gateways.
- Annunciation: Drives up to 32 remote 80-character annunciators (FDU-80, LCD2-80) and EIA-485 custom graphic interfaces (ACM/AEM-24AT, LDM-32 series) supporting up to 2,048 control points.
- Network Systems: Supports integration into standard NOTI-FIRE-NET configurations (up to 103 nodes) and High-Speed NOTI-FIRE-NET networks (up to 200 nodes).