Back to Product
FAQ

What is the loop capacity and power specification of the Notifier NFS2-640E?

Answer:
The Notifier NFS2-640E comes with 1 isolated intelligent SLC loop expandable to 2 loops, supporting up to 159 detectors and 159 modules per loop (636 devices maximum). It incorporates a 240 VAC power supply providing 3.0 A in standby and 6.0 A in alarm, four Class A/B NAC circuits, and a charger supporting 18 to 200 AH batteries (they are not included).

The Notifier NFS2-640E is an intelligent addressable fire alarm control panel designed for stand-alone or networked configurations. Key technical specifications include:

  • Signaling Line Circuits (SLC): Configured standard with 1 isolated intelligent SLC (Class A, B, or X), expandable to 2 loops via an expansion module.
  • Device Capacity: Supports up to 159 detectors and 159 modules per SLC, allowing 318 devices per loop and up to 636 addressable points per panel or network node.
  • Power Supply Rating: Built-in 240 VAC offline switching power supply rated at 3.0 A in standby and 6.0 A in alarm mode.
  • Notification Appliance Circuits: Four built-in Class A/B NAC circuits with selectable strobe synchronization for System Sensor, Wheelock, or Gentex devices.
  • Battery Charger: Supports secondary sealed lead-acid batteries ranging from 18 to 200 AH (they are not included), featuring real-time voltage and current monitoring on the panel display.
  • Event Logging: Dedicated nonvolatile memory storing an 800-event general history log alongside a separate 200-event alarm-only log.