Answer:
The card is compatible with Honeywell Morley-IAS ZXSe (ZX1Se, ZX2Se, ZX5Se) and legacy ZX series control panels. It supports both Class A return loops and Class B spur circuits, accommodating up to 99 detector addresses and 99 module addresses (198 total addressable points) per loop.
The Honeywell Morley-IAS 795-072-100 loop driver card provides direct hardware expansion across the Morley-IAS intelligent panel series:
- Morley-IAS ZX1Se: Supports 1 loop card (up to 460 mA total loop load).
- Morley-IAS ZX2Se: Expands from 1 to 2 loop cards (up to 460 mA per loop).
- Morley-IAS ZX5Se: Expands from 1 up to 5 loop cards (up to 460 mA per loop).
- Legacy ZX Series: Compatible with multi-protocol intelligent ZX panels.
Each driver card accommodates up to 198 individual devices running the Morley-IAS communication protocol, divided into a maximum of 99 analogue addressable sensors (optical smoke, thermal heat) and 99 control or interface modules (monitor modules, control modules, zone interfaces, and loop isolators). It supports both Class A (closed return) and Class B (open spur) wiring topologies. Note that while distinct networked panels can run different protocols across a facility, all loop driver cards fitted within a single ZXSe panel chassis must share the identical detector protocol.