Answer:
The HM-RHSE is designed to lock into the Honeywell B501AP plug-in base and interfaces with Honeywell Morley-IAS addressable fire alarm control panels running proprietary analog communication protocols. It also supports remote LED annunciators via its 22.5 V DC remote output terminals.
The Honeywell HM-RHSE thermal detector operates as an integral component within structured Honeywell addressable fire detection loops:
- Mounting Base Compatibility: Mounts directly into the standard Honeywell B501AP plug-in mounting base using a twist-to-lock action. The base features an integrated anti-tamper locking mechanism to prevent unauthorized head removal.
- Fire Alarm Control Panels: Must be connected to compatible Honeywell Morley-IAS intelligent fire alarm control panels (FACPs) running proprietary Morley-IAS analog addressable communications protocols.
- Remote Output Annunciation: Includes dedicated output terminals supporting standard remote LED indicators, providing 22.5 V DC at 10.8 mA under a 24 V DC loop supply.
- Cabling & Terminations: Terminates standard fire-rated loop conductors up to 2.5 mm² directly at the B501AP base terminal blocks.