Answer:
The detector is compatible with standard 2-wire conventional fire alarm control panels supplying 9V DC to 33V DC and installs on the included standard 100 mm mounting base.
Compatibility and mounting parameters for this detector comprise:
- Control Panels: Engineered to operate with standard conventional fire alarm control panels supplying zone loop voltages between 9V DC and 33V DC.
- Mounting Interface: Installs using a standard 100 mm ceiling mounting base (compatible with standard conventional bases such as the RE-314B normal base).
- Nominal Spacing: Designed for an installation spacing rating of 5 meters between detectors in standard open-area configurations.
- Remote Annunciation: Features a dedicated 15 mA open-collector remote output to drive an external indicator lamp outside closed rooms or above ceilings.