Answer:
The detector measures 100 mm in diameter by 46 mm in height with the included base and weighs 130 g (0.13 kg). It operates from 9V to 33V DC with an IP42 rating, triggering at a 59°C (138°F) fixed threshold or an 11.1°C/min (20°F/min) rate of rise.
The conventional heat detector (SKU: KTI07001001HTDT) features the following verified physical, mechanical, and electrical specifications:
- Dimensions: 100 mm diameter × 46 mm height (measured with base attached).
- Weight: 130 grams (0.13 kg) including base.
- Enclosure Protection: IP42 ingress protection classification.
- Operating Voltage: 9V DC to 33V DC.
- Current Consumption: 50 µA standby current, 170 µA start-up current (60-second start-up time), and 90 mA maximum alarm current.
- Remote Output: 15 mA maximum via open collector circuit.
- Thermal Activation Limits: Fixed thermal rating of 59°C (138°F) and Rate of Rise (ROR) threshold of 11.1°C per minute (20°F per minute).
- Operating & Storage Conditions: Operating temperature range from -10°C to 37.8°C; storage temperature range from -10°C to 60°C; operating relative humidity from 0% to 95% RH (non-condensing).
- Internal Sensor Sampling Cycle: 5 seconds.