The eSSL X7 is an autonomous, single-door access control terminal designed for direct surface mounting. Successful field commissioning requires strict adherence to physical mounting dimensions, input power ratings, and proper interface termination for third-party peripheral hardware.
Physical Mounting and Environmental Placement
The device features a compact, square enclosure measuring 88 mm in length, 88 mm in width, and 35 mm in depth. It is engineered for flat-surface installation onto interior architectural walls, entry partitions, or electrical junction backboxes adjacent to the secured access point.
Installers must verify that the ambient operating environment conforms to specified tolerances: an ambient operating temperature between 0°C and 40°C, and a non-condensing relative humidity range between 20% and 80%. The compact 88 mm x 88 mm x 35 mm footprint allows mounting on narrow mullions, server room entry points, office cabins, and commercial doors without obstructing surrounding frames.
Power Supply Wiring Requirements
The eSSL X7 operates on a dedicated external power supply delivering 12V DC at a minimum current rating of 3A. Because the terminal functions entirely as a standalone system without reliance on a host PC or centralized controller board, a clean and regulated direct current supply is essential.
Ensure power wiring polarity is verified prior to energizing the unit. Supplying a regulated 12V DC 3A line ensures consistent operation across the optical fingerprint sensor, internal processing circuitry, integrated keypad, and connected locking hardware relays.
Peripheral Hardware Terminal Integration
The terminal features an integrated physical connection interface to coordinate all door hardware elements directly from the unit:
- Electric Lock Interface: Onboard relay contacts connect directly to third-party electric locking mechanisms. The interface is compatible with electromagnetic locks (EM locks), electric drop bolts, and electric strike locks.
- Exit Button Input: Dedicated terminals wire directly to standard push-to-exit request buttons, allowing momentary relay activation for internal egress.
- Door Sensor Interface: Accepts input from external normally-open (NO) or normally-closed (NC) magnetic door position contacts to track opening status and detect forced-door conditions.
- Alarm Output: Connects to external audible alarms or visual indicators to signal unauthorized door status or tampering.
- Doorbell Connection: Provides direct wiring terminals for an external wired doorbell unit triggered via the terminal keypad.
Interface Connections Overview
| Interface Port | Compatible Hardware | Functional Purpose |
|---|---|---|
| Power Input | 12V DC, 3A Power Source | System power and internal component operation |
| Lock Output | EM locks, electric bolts, electric strikes | Third-party electric lock control |
| Exit Button | Request-to-exit momentary switch | Egress release triggering |
| Door Sensor | NO / NC magnetic door contact | Door open/closed status monitoring |
| Alarm Output | External audible/visual alarm | Intrusion and forced entry signaling |
| Doorbell Output | External wired chime/bell | Visitor notification signaling |
Standalone System Commissioning
Because the eSSL X7 operates as a standalone biometric access controller, it requires no host computer connection, network drops, or external controller software during setup. All user registration and configuration steps occur directly on the integrated keypad and optical scanner.
Commissioning engineers can enroll up to 500 fingerprint templates utilizing the onboard optical sensor and Finger V10.0 algorithm, register up to 500 standard 125 kHz RFID proximity cards, and configure up to 8 password groups. Verification modes can be structured locally for card, fingerprint, password, password + fingerprint, or password + card authentication.