Answer:
The assembled detector and DB-01 base measure 100 mm in diameter by 53.3 mm in height and weigh approximately 110 g. It operates at 24VDC nominal loop voltage (16VDC to 28VDC) with a quiescent standby current of ≤0.6 mA and an operating temperature range of -10°C to +50°C at up to 95% relative humidity (non-condensing).
The GST DI-9103E intelligent heat detector paired with the DB-01 common base is engineered with the following technical specifications:
- Dimensions: 100 mm diameter × 53.3 mm height (assembled detector with DB-01 base). The standalone DB-01 base measures 100 mm diameter × 14 mm height.
- Weight: Approximately 110 g for the complete assembly (DB-01 base alone weighs approximately 55 g).
- Operating Voltage: 24VDC nominal loop voltage across an allowable range of 16VDC to 28VDC.
- Current Consumption: Standby current is ≤0.6 mA; alarm current is ≤1.5 mA without an external remote indicator and ≤3.5 mA when powering a remote indicator.
- Operating Environment: Operating temperature range is -10°C to +50°C with relative humidity up to 95% non-condensing.
- Ingress Protection: Rated IP2X for indoor installations.
- Cabling & Terminals: Connects via terminals 1 and 3 on the DB-01 base using fire-rated non-polarized loop cabling (minimum 1.0 mm², recommended 1.5 mm² up to 1500 meters).